CJX2 contactor
CJX2 contactor
CJX2 contactor
CJX2 contactor
CJX2 contactor
CJX2 contactor

CJX2 contactor

CJX2 Contactor (LC1) (AC/DC contactor, hereinafter referred to as contactor), mainly used for the circuit of AC 50Hz (or 60Hz), the voltage to 660V, the rated operating current to 95A in the utilization category of AC-3, 400V (380V), for the remote on and off circuit, frequent start and control AC motor, and combine with the appropriate thermal relay to form electromagnetic starter to protect the circuit may occur overload operation.

  • Product Description
  • Specifications
  • Product Features
  • More Details

Product Description


Structural features

1. The contactor for the protective type, the action structure for the direct action, the contact for the double breakpoint, with a small size, light weight, low power consumption, long life, safe and reliable;

2. the AC/DC contactor can compose mechanical reversible interlocking magnetic starter, star delta decompression starter, can also compose a variety of derivative products with auxiliary contact group, air delay head and so on according to the users.

3. It can use building block installation to add auxiliary contact group, air delay head (the delay range shown in Table 4), thermal relays and other accessories, combined into a variety of derivative products (see Table 3).

4. SR2 series surge suppressor with a significant function of surge suppression, and used with CJX2 series contact, can effectively protect the contactor to extend the service life. And can avoid interference from the surge pulse to the PC and other related electronic control system.

SR2-A for CJX2 series 09A ~ 32A AC/DC contactor, the specific specifications are:

SR2-A 24V~48V AC, DC
SR2-A 100V~250V AC, DC
SR2-A 380V~440V AC, DC

5. The AC/DC contactor has a small size, light weight, low power consumption, high life, safe and reliable and so on.

6. The AC/DC contactor body has a pair of normally open or normally closed auxiliary contact in the 32A and below, a pair of normally open and normally closed auxiliary contact in the 40A and above. In addition, it can add F4 auxiliary contact group (two or four groups) or air delay head on the top, add a NCF1-11C on either side, their combinations (see Table 4 and Table 5).

7.Except for the screw installation, the contactor can also use 35mm (CJX2-09 ~ 95) and 75mm (CJX2-40 ~ 95) concave standard rail installation.


Specifications

AC/DC contactor model of Schneider LC1

AC/DC contactor model of  CJX2

LC1-D09M7C

CJX2-09

LC1-D12M7C

CJX2-12

LC1-D18M7C

CJX2-18

LC1-D25M7C

CJX2-25

LC1-D32M7C

CJX2-32

LC1-D40M7C

CJX2-40

LC1-D50M7C

CJX2-50

LC1-D65M7C

CJX2-65

LC1-D80M7C

CJX2-80

LC1-D95M7C

CJX2-95

JCX2 AC contactor of the main parameters and technical performance indicators (see Table 1).

Model

CJX2-09

CJX2-12

CJX2-18

CJX2-25

CJX2-32

CJX2-40

CJX2-50

CJX2-65

CJX2-80

CJX2-95

Rated operating current
(A)

380/400V

AC-3

9

12

18

25

32

40

50

65

80

95

AC-4

3.5

5

7.7

8.5

12

18.5

24

28

37

44

600/690V

AC-3

6.6

8.9

12

18

21

34

39

42

49

49

AC-4

1.5

2

3.8

4.4

7.5

9

12

14

17.3

21.3

Conventional free air heating current(A)

20

20

32

40

50

60

80

80

95

95

Rated insulation voltage(V)

690

Controllable three-phase

squirrel cage motor power
(AC-3)kW

220/230V

2.2

3

4

5.5

7.5

11

15

18.5

22

25

380/400V

4

5.5

7.5

11

15

18.5

22

30

37

45

660/690V

5.5

7.5

10

15

18.5

30

37

37

45

45

Operating frequency
(times/h)

Electrical life

AC-3

1200

1200

1200

1200

600

600

600

600

600

600

AC-4

300

Mechanical life

3600

Electrical life
(10000 times)

AC-3

100

100

100

100

80

80

60

60

60

60

AC-4

20

20

20

20

20

15

15

15

10

10

Mechanical life(10000 times)

1000

1000

1000

1000

800

800

800

800

600

600

Distribution fuse Model

RT16-20

RT16-20

RT16-32

RT16-40

RT16-50

RT16-63

RT16-80

RT16-80

RT16-100

RT16-125

Cold-pressed terminal


Number

1

2

1

2

1

2

1

2

1

2

1

2

1

2

1

2

1

2

1

2

Non-prefabricated

terminal flexible wire

mm²

1/2.5

1/2.5

1/2.5

1/2.5

1.5/4

1.5/4

1.5/4

1.5/4

2.5/6

2.5/6

6/25

4/10

6/25

4/10

6/25

4/10

10/35

6/16

10/35

6/16

Prefabricated

terminal flexible wire

1/4

1/2.5

1/4

1/2.5

1.5/6

1.5/4

1.5/10

1.5/6

2.5/10

2.5/6

6/25

4/10

6/25

4/10

6/25

4/10

10/35

6/16

10/35

6/16

Non-prefabricated

terminal hard wire

1/4

1/4

1/4

1/4

1.5/6

1.5/6

1.5/6

1.5/6

2.5/10

2.5/10

6/25

4/10

6/25

4/10

6/25

4/10

10/35

6/16

10/35

6/16

AC coil power

50Hz

Pull-in(VA)

70

70

70

110

110

200

200

200

200

200

Hold(VA)

9.0

9.0

9.5

14.0

14.0

57.0

57.0

57.0

57.0

57.0

Power(W)

1.8~2.7

1.8~2.7

3~4

3~4

3~4

6~10

6~10

6~10

6~10

6~10

Operating range

Pull-in voltage: 85%Us~110Us;

Release voltage: 20%Us~75Us

Basic parameters of

auxiliary contact

AC-15:le:0.95A 380V/400V ;

DC-13:le:0.15A 220V/250V lth:10A

4.2 Electrical life curve.

图片1

4.3 Coil rated power supply voltage Us and code (see Table 2).

Coil voltage Us(V)

24

36

42

48

110

127

220

230

240

380

400

415

440

480

600

50Hz

B5

C5

D5

E5

F5

G5

M5

P5

U5

Q5

V5

N5

R5

T5

X5

60Hz

B6

C6

D6

E6

F6

G6

M6

P6

U6

Q6

V6

N6

R6

T6

X6

50Hz/60Hz

B7

C7

D7

E7

F7

G7

M7

P7

U7

Q7

V7

N7

R7

T7

X7







Product Features

1. The contactor for the protective type, the action structure for the direct action, the contact for the double breakpoint, with a small size, light weight, low power consumption, long life, safe and reliable;

2. the AC/DC contactor can compose mechanical reversible interlocking magnetic starter, star delta decompression starter, can also compose a variety of derivative products with auxiliary contact group, air delay head and so on according to the users.

3. It can use building block installation to add auxiliary contact group, air delay head (the delay range shown in Table 4), thermal relays and other accessories, combined into a variety of derivative products (see Table 3).

4. SR2 series surge suppressor with a significant function of surge suppression, and used with CJX2 series contact, can effectively protect the contactor to extend the service life. And can avoid interference from the surge pulse to the PC and other related electronic control system.

SR2-A for CJX2 series 09A ~ 32A AC/DC contactor, the specific specifications are:
SR2-A 24V~48V AC, DC
SR2-A 100V~250V AC, DC
SR2-A 380V~440V AC, DC

5. The AC/DC contactor has a small size, light weight, low power consumption, high life, safe and reliable and so on.

6. The AC/DC contactor body has a pair of normally open or normally closed auxiliary contact in the 32A and below, a pair of normally open and normally closed auxiliary contact in the 40A and above. In addition, it can add F4 auxiliary contact group (two or four groups) or air delay head on the top, add a NCF1-11C on either side, their combinations (see Table 4 and Table 5).

7.Except for the screw installation, the contactor can also use 35mm (CJX2-09 ~ 95) and 75mm (CJX2-40 ~ 95) concave standard rail installation.

Videos

Where you need an efficient solution, there you need an inquiry

Do you need a professional team to provide you with solutions? Contact us for a quote

×

Contact Us

*We respect your privacy. When you submit your contact information, we agree to only contact you in accordance with our Privacy Policy.

×

Inquire

*Name
*Email
*Company Name
*Tel
*Message

*We respect your privacy. When you submit your contact information, we agree to only contact you in accordance with our Privacy Policy.