CJX2 contactor
CJX2 Contactor (LC1) (AC/DC contactor, hereinafter referred to as contactor), mainly used for the circuit of AC 50Hz (or 60Hz), the voltage to 660V, the rated operating current to 95A in the utilization category of AC-3, 400V (380V), for the remote on and off circuit, frequent start and control AC motor, and combine with the appropriate thermal relay to form electromagnetic starter to protect the circuit may occur overload operation.
- Product Description
- Specifications
- Product Features
- More Details
Product Description
Structural features
1. The contactor for the protective type, the action structure for the direct action, the contact for the double breakpoint, with a small size, light weight, low power consumption, long life, safe and reliable;
2. the AC/DC contactor can compose mechanical reversible interlocking magnetic starter, star delta decompression starter, can also compose a variety of derivative products with auxiliary contact group, air delay head and so on according to the users.
3. It can use building block installation to add auxiliary contact group, air delay head (the delay range shown in Table 4), thermal relays and other accessories, combined into a variety of derivative products (see Table 3).
4. SR2 series surge suppressor with a significant function of surge suppression, and used with CJX2 series contact, can effectively protect the contactor to extend the service life. And can avoid interference from the surge pulse to the PC and other related electronic control system.
SR2-A for CJX2 series 09A ~ 32A AC/DC contactor, the specific specifications are:
SR2-A 24V~48V AC, DC
SR2-A 100V~250V AC, DC
SR2-A 380V~440V AC, DC
5. The AC/DC contactor has a small size, light weight, low power consumption, high life, safe and reliable and so on.
6. The AC/DC contactor body has a pair of normally open or normally closed auxiliary contact in the 32A and below, a pair of normally open and normally closed auxiliary contact in the 40A and above. In addition, it can add F4 auxiliary contact group (two or four groups) or air delay head on the top, add a NCF1-11C on either side, their combinations (see Table 4 and Table 5).
7.Except for the screw installation, the contactor can also use 35mm (CJX2-09 ~ 95) and 75mm (CJX2-40 ~ 95) concave standard rail installation.
Specifications
AC/DC contactor model of Schneider LC1 | AC/DC contactor model of CJX2 |
LC1-D09M7C | CJX2-09 |
LC1-D12M7C | CJX2-12 |
LC1-D18M7C | CJX2-18 |
LC1-D25M7C | CJX2-25 |
LC1-D32M7C | CJX2-32 |
LC1-D40M7C | CJX2-40 |
LC1-D50M7C | CJX2-50 |
LC1-D65M7C | CJX2-65 |
LC1-D80M7C | CJX2-80 |
LC1-D95M7C | CJX2-95 |
JCX2 AC contactor of the main parameters and technical performance indicators (see Table 1).
Model | CJX2-09 | CJX2-12 | CJX2-18 | CJX2-25 | CJX2-32 | CJX2-40 | CJX2-50 | CJX2-65 | CJX2-80 | CJX2-95 | ||||||||||||
Rated operating current | 380/400V | AC-3 | 9 | 12 | 18 | 25 | 32 | 40 | 50 | 65 | 80 | 95 | ||||||||||
AC-4 | 3.5 | 5 | 7.7 | 8.5 | 12 | 18.5 | 24 | 28 | 37 | 44 | ||||||||||||
600/690V | AC-3 | 6.6 | 8.9 | 12 | 18 | 21 | 34 | 39 | 42 | 49 | 49 | |||||||||||
AC-4 | 1.5 | 2 | 3.8 | 4.4 | 7.5 | 9 | 12 | 14 | 17.3 | 21.3 | ||||||||||||
Conventional free air heating current(A) | 20 | 20 | 32 | 40 | 50 | 60 | 80 | 80 | 95 | 95 | ||||||||||||
Rated insulation voltage(V) | 690 | |||||||||||||||||||||
Controllable three-phase squirrel cage motor power | 220/230V | 2.2 | 3 | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 25 | |||||||||||
380/400V | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | ||||||||||||
660/690V | 5.5 | 7.5 | 10 | 15 | 18.5 | 30 | 37 | 37 | 45 | 45 | ||||||||||||
Operating frequency | Electrical life | AC-3 | 1200 | 1200 | 1200 | 1200 | 600 | 600 | 600 | 600 | 600 | 600 | ||||||||||
AC-4 | 300 | |||||||||||||||||||||
Mechanical life | 3600 | |||||||||||||||||||||
Electrical life | AC-3 | 100 | 100 | 100 | 100 | 80 | 80 | 60 | 60 | 60 | 60 | |||||||||||
AC-4 | 20 | 20 | 20 | 20 | 20 | 15 | 15 | 15 | 10 | 10 | ||||||||||||
Mechanical life(10000 times) | 1000 | 1000 | 1000 | 1000 | 800 | 800 | 800 | 800 | 600 | 600 | ||||||||||||
Distribution fuse Model | RT16-20 | RT16-20 | RT16-32 | RT16-40 | RT16-50 | RT16-63 | RT16-80 | RT16-80 | RT16-100 | RT16-125 | ||||||||||||
Cold-pressed terminal | Number | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | |
Non-prefabricated terminal flexible wire | mm² | 1/2.5 | 1/2.5 | 1/2.5 | 1/2.5 | 1.5/4 | 1.5/4 | 1.5/4 | 1.5/4 | 2.5/6 | 2.5/6 | 6/25 | 4/10 | 6/25 | 4/10 | 6/25 | 4/10 | 10/35 | 6/16 | 10/35 | 6/16 | |
Prefabricated terminal flexible wire | 1/4 | 1/2.5 | 1/4 | 1/2.5 | 1.5/6 | 1.5/4 | 1.5/10 | 1.5/6 | 2.5/10 | 2.5/6 | 6/25 | 4/10 | 6/25 | 4/10 | 6/25 | 4/10 | 10/35 | 6/16 | 10/35 | 6/16 | ||
Non-prefabricated terminal hard wire | 1/4 | 1/4 | 1/4 | 1/4 | 1.5/6 | 1.5/6 | 1.5/6 | 1.5/6 | 2.5/10 | 2.5/10 | 6/25 | 4/10 | 6/25 | 4/10 | 6/25 | 4/10 | 10/35 | 6/16 | 10/35 | 6/16 | ||
AC coil power | 50Hz | Pull-in(VA) | 70 | 70 | 70 | 110 | 110 | 200 | 200 | 200 | 200 | 200 | ||||||||||
Hold(VA) | 9.0 | 9.0 | 9.5 | 14.0 | 14.0 | 57.0 | 57.0 | 57.0 | 57.0 | 57.0 | ||||||||||||
Power(W) | 1.8~2.7 | 1.8~2.7 | 3~4 | 3~4 | 3~4 | 6~10 | 6~10 | 6~10 | 6~10 | 6~10 | ||||||||||||
Operating range | Pull-in voltage: 85%Us~110Us; Release voltage: 20%Us~75Us | |||||||||||||||||||||
Basic parameters of auxiliary contact | AC-15:le:0.95A 380V/400V ; DC-13:le:0.15A 220V/250V lth:10A |
4.2 Electrical life curve.
4.3 Coil rated power supply voltage Us and code (see Table 2).
Coil voltage Us(V) | 24 | 36 | 42 | 48 | 110 | 127 | 220 | 230 | 240 | 380 | 400 | 415 | 440 | 480 | 600 |
50Hz | B5 | C5 | D5 | E5 | F5 | G5 | M5 | P5 | U5 | Q5 | V5 | N5 | R5 | T5 | X5 |
60Hz | B6 | C6 | D6 | E6 | F6 | G6 | M6 | P6 | U6 | Q6 | V6 | N6 | R6 | T6 | X6 |
50Hz/60Hz | B7 | C7 | D7 | E7 | F7 | G7 | M7 | P7 | U7 | Q7 | V7 | N7 | R7 | T7 | X7 |
Product Features
1. The contactor for the protective type, the action structure for the direct action, the contact for the double breakpoint, with a small size, light weight, low power consumption, long life, safe and reliable;
2. the AC/DC contactor can compose mechanical reversible interlocking magnetic starter, star delta decompression starter, can also compose a variety of derivative products with auxiliary contact group, air delay head and so on according to the users.
3. It can use building block installation to add auxiliary contact group, air delay head (the delay range shown in Table 4), thermal relays and other accessories, combined into a variety of derivative products (see Table 3).
4. SR2 series surge suppressor with a significant function of surge suppression, and used with CJX2 series contact, can effectively protect the contactor to extend the service life. And can avoid interference from the surge pulse to the PC and other related electronic control system.
SR2-A for CJX2 series 09A ~ 32A AC/DC contactor, the specific specifications are:
SR2-A 24V~48V AC, DC
SR2-A 100V~250V AC, DC
SR2-A 380V~440V AC, DC
5. The AC/DC contactor has a small size, light weight, low power consumption, high life, safe and reliable and so on.
6. The AC/DC contactor body has a pair of normally open or normally closed auxiliary contact in the 32A and below, a pair of normally open and normally closed auxiliary contact in the 40A and above. In addition, it can add F4 auxiliary contact group (two or four groups) or air delay head on the top, add a NCF1-11C on either side, their combinations (see Table 4 and Table 5).
7.Except for the screw installation, the contactor can also use 35mm (CJX2-09 ~ 95) and 75mm (CJX2-40 ~ 95) concave standard rail installation.

Videos
Related Solutions
-
Mining Industry
The mining industry involves the extraction of valuable minerals or other geological materials from the Earth. The industry plays a crucial role in providing raw materials for various sectors, including construction, manufacturing, and energy production. However, the mining industry faces several challenges
-
Rail Transportation
Rail transportation plays a vital role in the logistics and mobility infrastructure of countries worldwide. It offers an efficient and environmentally friendly way to transport goods and passengers over long distances.
-
Server Room
Server rooms are critical facilities that house computer servers, networking equipment, and data storage systems. They play a pivotal role in ensuring the smooth operation of IT infrastructure for businesses.
-
Drilling Platform
Drilling platforms are essential structures in the oil and gas industry, enabling the extraction of hydrocarbons from beneath the Earth's surface. These platforms can be fixed or floating and are designed to withstand harsh marine environments.
-
Mining Equipment
The development of mining equipment has been driven by the need to extract resources from increasingly difficult-to-reach locations and to process larger quantities of ore with greater efficiency.
-
Industrial Manufacturing
Today, the industry faces new challenges and opportunities, driven by technological advancements, globalization, and changing consumer demands.
-
Power Industry
With the growth of population and industrialization, the demand for electricity has been constantly increasing. This has led to the expansion and modernization of the power industry across the globe.
-
Building Automation
Building automation started with simple mechanical controls and has evolved into sophisticated digital systems that integrate various technologies to enhance building performance and occupant comfort.
Related Videos
-
DC solution
-
Motor protection solution
-
Electrical protection solution
-
The future of electrical safety: Miniature circuit breakers from Shanghai Dada Electric Co., Ltd.
In an age where electrical safety is paramount, the role of miniature circuit breakers (MCBs) cannot be overstated. Designed to protect electrical circuits from overloads and short circuits, these ess
-
Unleashing the power of safety: Shanghai Dada Electric Co., Ltd. DC series miniature circuit breakers
In an age where electrical safety and efficiency are critical, the DC series of miniature circuit breakers (MCBs) from Shanghai Dada Electric Co., Ltd. stands out as a model of innovation and reliabil