DAB6-125
DAB6-125 is such features as delicate appearance, light weight, excellent and reliableperformance, high breaking capacity, rapid tripping and mounted by rail. Its enclosure and com-ponents adopts high fire-retarding and shock-resistance plastic of long durability. It mainly servesfor protecting the circuits of AC 50Hz, 230V of single pole, 400V of two poles or three or fourpoles from overload or short-circuit, and also for unfrequent making and breaking electricalapparatus and lighting circuit.It conforms with the standards of IEC60947-2.
- Product Description
- Specifications
- Product Features
- More Details
Product Description
Advantages
· Two types of overload and short circuit protection.
· Independent contact position indicator.
· DIN rail latch with a double fixed position.
· Wide range of operating temperatures from –40 to +50° С.
· Updated wider engagement lever with improved contact area.
· Notches on terminal clamps provide for lowering thermal losses and boosting the mechanical stability of connection.
· Higher switching capacity of 10 kA provides for installing DAB6-125 as incoming circuit breakers.
Specifications
Technical Features
MCB DAB6-125 | |||||||
For protection of general power distribution (IEC/EN 60898-1) | | ||||||
Poles | 1P | 2P | 3P | 4P | |||
Electrical performance | |||||||
Functions | short circuit protection,overload protection,isolationg,control | ||||||
Rated frequency f(Hz) | 50-60Hz | ||||||
Rated working voltage Ue(V) AC | 230/400 | 400 | |||||
Rated current In(A) | 63,80,100,125 | ||||||
Rated insulated voltage Ui (V) | 500 | ||||||
Impulse withstand voltage Uimp( kV) | 4 | ||||||
Instantaneous tripping type | DAB6-125N | B/C/D | |||||
DAB6-125H | B/C/D | ||||||
Rated short circuit Icn(kA) | DAB6-125N | 6 | |||||
DAB6-125H | 10 | ||||||
Release type | Thermal magnetic type | ||||||
Service life(O~C) | Mechanical | Actual value | 8500 | ||||
Standard value | 4000 | ||||||
Electrical | Actual value | 1500 | |||||
Standard value | 1000 | ||||||
Connection and installation | |||||||
Protectiom degree | IP20 | ||||||
Wire(mm²) | 1~35 | ||||||
Working temperature | -5~+40℃ | ||||||
Resistance to humidity and heat | Class 2 | ||||||
Altitude above sea | ≤2000 | ||||||
Relative humidity | +20℃ ,≤90% ;+40℃ ,≤50% | ||||||
Pollution degree | 2 | ||||||
Installation environment | Avoid obvious shock and vibration | ||||||
Installation class | ClassⅡ , ClassⅢ | ||||||
Mounting | DIN35 rail | ||||||
Dimensions(mm) (WxHxL) | a | 27 | 54 | 81 | 108 | ||
b | 80 | 80 | 80 | 80 | |||
c | 73 | 73 | 73 | 73 |
>> The over-current protection property
Ambient Temperature | Initial Status | Test Current | Expected Result | Expected Result | NOte |
40±2oC | Cold position | 1.05In(In≤63A) | t≤1h | Non-release | - |
Cold position | 1.05In (In[63A) | t≤2h | Non-release | - | |
Carried out immedi-ately after previous test | 1.30In(In≤63A) | t < 1h | Release | Current smoothlyrises to specified value within 5s | |
1.30In (In>63A) | t < 2h | Release | |||
-5~+40oC | Cold position | 8.00In | t≤0.2s | Non-release | - |
Cold position | 12.00In | t< 0.2s | Non-release | - |
Applicable conducting wire
Rated current(A) | Nominal cross section of wire mm2 |
63A | 16 |
80A | 25 |
100A | 35 |
Product Features
· Two types of overload and short circuit protection.
· Independent contact position indicator.
· DIN rail latch with a double fixed position.
· Wide range of operating temperatures from –40 to +50° С.
· Updated wider engagement lever with improved contact area.
· Notches on terminal clamps provide for lowering thermal losses and boosting the mechanical stability of connection.
· Higher switching capacity of 10 kA provides for installing DAB6-125 as incoming circuit breakers.

Videos
Related Solutions
-
Mining Industry
The mining industry involves the extraction of valuable minerals or other geological materials from the Earth. The industry plays a crucial role in providing raw materials for various sectors, including construction, manufacturing, and energy production. However, the mining industry faces several challenges
-
Rail Transportation
Rail transportation plays a vital role in the logistics and mobility infrastructure of countries worldwide. It offers an efficient and environmentally friendly way to transport goods and passengers over long distances.
-
Server Room
Server rooms are critical facilities that house computer servers, networking equipment, and data storage systems. They play a pivotal role in ensuring the smooth operation of IT infrastructure for businesses.
-
Drilling Platform
Drilling platforms are essential structures in the oil and gas industry, enabling the extraction of hydrocarbons from beneath the Earth's surface. These platforms can be fixed or floating and are designed to withstand harsh marine environments.
-
Mining Equipment
The development of mining equipment has been driven by the need to extract resources from increasingly difficult-to-reach locations and to process larger quantities of ore with greater efficiency.
-
Industrial Manufacturing
Today, the industry faces new challenges and opportunities, driven by technological advancements, globalization, and changing consumer demands.
-
Power Industry
With the growth of population and industrialization, the demand for electricity has been constantly increasing. This has led to the expansion and modernization of the power industry across the globe.
-
Building Automation
Building automation started with simple mechanical controls and has evolved into sophisticated digital systems that integrate various technologies to enhance building performance and occupant comfort.
Related Videos
-
DC solution
-
Motor protection solution
-
Electrical protection solution
-
The future of electrical safety: Miniature circuit breakers from Shanghai Dada Electric Co., Ltd.
In an age where electrical safety is paramount, the role of miniature circuit breakers (MCBs) cannot be overstated. Designed to protect electrical circuits from overloads and short circuits, these ess
-
Introduction to DAB6-63 Circuit Breakers: A New Standard in Electrical Safety
In the evolving field of electrical safety and efficiency, Shanghai Dada Electric Co., Ltd. is at the forefront with over 30 years of production experience. Our commitment to innovation and quality ha
-
Improve your electrical solutions with SH distribution boxes from Shanghai Dada Electric Co., Ltd.
In the ever-evolving world of electrical solutions, the importance of reliable, efficient power distribution systems cannot be overstated. Shanghai Dada Electric Co., Ltd. is a leader in this industry