JR20 Thermal Overload Relay
JR20 Thermal Overload Relay are suitable for circuits with AC 50Hz, voltages up to 660V, and currents up to 630A, to protect against overload, phase failure and three phase unbalance of AC motor. With phase-failure protection, temperature compensation, manual or auto reset, action tripping flexibility check, action tripping indication, disconnection check button and other functions. Products meet the GB14048.4.
- Product Description
- Specifications
- Product Features
- More Details
Product Description
JR20 Thermal Overload Relay are suitable for circuits with AC 50Hz, voltages up to 660V, and currents up to 630A, to protect against overload, phase failure and three phase unbalance of AC motor. With phase-failure protection, temperature compensation, manual or auto reset, action tripping flexibility check, action tripping indication, disconnection check button and other functions. Products meet the GB14048.4.
Specifications
Structural Feature
Internal structure: Insert combination or independent structure; three-dimensional structure, pull spring blade jump action mechanism; with phase failure and temperature compensation structure.
Installation operation: with action tripping flexibility inspection, action tripping indication and disconnection inspection and other functions; optional manual reset and automatic reset; normally closed and normally open auxiliary contacts insulated and separated
Model | Rated insulation voltage Ui (V) | Thermoelement | Rated current range (A) | Corresponding AC contactor |
JR20-10 | 660 | 1R | 0.1~0.13~0.15 | CJ20-10 |
2R | 0.15~0.19~0.23 | |||
3R | 0.23~0.29~0.35 | |||
4R | 0.35~0.44~0.53 | |||
5R | 0.53~0.67~0.8 | |||
6R | 0.8~1~1.2 | |||
7R | 1.2~1.5~1.8 | |||
8R | 1.8~2.2~2.6 | |||
9R | 2.6~3.2~3.8 | |||
10R | 3.2~4~4.8 | |||
11R | 4~5~6 | |||
12R | 5~6~7 | |||
13R | 6~7.2~8.4 | |||
14R | 7~8.6~10 | |||
15R | 8.6~10~11.6 | |||
JR20-16 | 1S | 3.6~4.5~5.4 | CJ20-16 | |
2S | 5.4~6.7~8 | |||
3S | 8~10~12 | |||
4S | 10~12~14 | |||
5S | 12~14~16 | |||
6S | 14~16~18 | |||
JR20-25 | 1T | 7.8~9.7~11.6 | CJ20-25 | |
2T | 11.6~14.3~17 | |||
3T | 17~21~25 | |||
4T | 21~25~29 | |||
JR20-63 | 1U | 16~20~24 | CJ20-40 | |
2U | 24~30~36 | |||
3U | 32~40~47 | |||
4U | 40~47~55 | |||
5U | 47~55~62 | |||
6U | 55~63~71 | |||
JR20-160 | 1W | 33~40~47 | CJ20-100 | |
2W | 47~55~63 | |||
3W | 63~74~84 | |||
4W | 74~86~98 | |||
5W | 85~100~115 | |||
6W | 100~115~130 | |||
7W | 115~132~150 | |||
8W | 130~150~170 | |||
9W | 144~160~176 | |||
JR20-250 | 1X | 130~150~170 | CJ20-250 | |
2X | 167~200~250 | |||
JR20-400 | 1Y | 200~250~300 | CJ20-400 | |
2Y | 267~335~400 | |||
JR20-630 | 1Z | 320~400~480 | CJ20-630 | |
2Z | 420~525~630 |
Note: The 10R and below specification in JR20-10 does not include a phase failure protection device.
Basic parameters of auxiliary circuit
Utilization Category | Rated frequency | Rated insulation voltage (Ui) | Rated operational voltage (Ue) | Rated operational current (Ie) | Conventional thermal current | Auxiliary contact |
AC-15 | 50Hz | 380V | 127V | 2.83A | 6A | NC 95-96 |
220V | 1.64A | |||||
380V | 0.95A | |||||
220V | 0.82A | 6A | NO 97-98 | |||
380V | 0.47A |
Operation characteristics
No. | Setting current multiples | Action time | Initial condition | ||
Operation characteristics when negative each phase is balanced | |||||
1 | 1.05 | No action in 2h | Cold | ||
2 | 1.2 | Action in 2h | Thermal (after No. 1 test) | ||
3 | 1.5 | <2min | <4min | Thermal (after No. 1 test) | |
4 | 7.2 | 2s<Tp≤10s | 4s<Tp≤10s | Cold | |
5 | 1.0 | No action in 2h | Cold | ||
6 | 1.2 | Action in 2h | Thermal (after No. 5 test) | ||
7 | 1.05 | No action in 2h | Cold | ||
8 | 1.3 | Action in 2h | Thermal (after No. 7 test) | ||
Operation characteristics when negative each phase is unbalanced | |||||
Any two phase | Third phase | ||||
1 | 1.10 | 0.9 | No action in 2h | Cold | |
2 | 1.15 | 0 | Action in 2h | Thermal (after No. 1 test) |
Outline and lnstallation Dimension
1. Outline and lnstallation Dimension of JR20-10Z/JR20-16Z/JR20-25Z/JR20-63Z/JR20-160Z
Thermal Relay | A | B | C | D | E | F | G | H | K | a | M1 | M2 | φ |
Model | Feature | ||||||||||||
JR20-10 | Z | 44 | 77.5 | 101 | 57.8 | 10 | 4.5 | 13.9 | 32 | ||||
L | 44 | 70 | 101 | 46 | 14 | 4.5 | 8.9 | 32 | M5 | ||||
G | 44 | 70 | 112 | 53 | 14 | 8.9 | M5 | ||||||
JR20-16 | Z | 44 | 78 | 101 | 71 | 14 | 4.5 | 12.9 | 32 | ||||
L | 44 | 70 | 101 | 46 | 14 | 4.5 | 8.9 | 32 | M5 | ||||
G | 44 | 70 | 112 | 53 | 14 | 8.9 | 5.2 | M5 | |||||
JR20-25 | Z | 47.5 | 82.5 | 117 | 66 | 20.5 | 4.5 | 32 | |||||
L | 44 | 70 | 117 | 46 | 14 | 8.9 | 5.5 | 32 | M5 | ||||
G | 44 | 70 | 117 | 53 | 14 | 5.5 | 8.9 | 6.5 | M5 | ||||
JR20-63 | Z | 64 | 90 | 117 | 82 | 20 | 5.5 | 46 | |||||
70 | 90 | 117 | 92 | 28 | 5.5 | 46 | |||||||
L | 65 | 80 | 117 | 62 | 23 | 5.5 | 46 | M6 | |||||
65 | 80 | 117 | 62 | 23 | 46 | M6 | |||||||
G | |||||||||||||
7 | |||||||||||||
JR20-160 | Z | 104 | 100 | 152 | 87.5 | 87.5 | 29 | 37 | M6 | M8 | 7 | ||
104 | 100 | 152 | 87.5 | 87.5 | 45 | 37 | M6 | M8 | |||||
L |
Product Features
Ambient temperature: The average value does not exceed +35°C in 24 hours.
Altitude: no more than 2000m.
Atmospheric conditions: The relative humidity does not exceed 50% at +40°C, and higher relative humidity may be allowed at lower temperatures. For example, 90% at 20°C, special measures should be taken for the occasional condensation due to temperature changes.
Pollution level: 3 levels.
Installation category: Class III.
Installation conditions: The inclination of the installation face and the vertical is not more than ±5°.In addition to mounting screws, the relay can also use 35mm standard rail.
Shock vibration: The relay should be installed and used in places where there is no significant shaking, shock and vibration.
Transportation, Storage: The relay should not be subject to severe impact and vibration during transportation, and it must not be affected by rain or snow in transportation and storage. Relays are suitable for transport and storage at -25°C ~ +55°C, and at +70°C for short periods (in 24h).

Videos
Related Solutions
-
Mining Industry
The mining industry involves the extraction of valuable minerals or other geological materials from the Earth. The industry plays a crucial role in providing raw materials for various sectors, including construction, manufacturing, and energy production. However, the mining industry faces several challenges
-
Rail Transportation
Rail transportation plays a vital role in the logistics and mobility infrastructure of countries worldwide. It offers an efficient and environmentally friendly way to transport goods and passengers over long distances.
-
Server Room
Server rooms are critical facilities that house computer servers, networking equipment, and data storage systems. They play a pivotal role in ensuring the smooth operation of IT infrastructure for businesses.
-
Drilling Platform
Drilling platforms are essential structures in the oil and gas industry, enabling the extraction of hydrocarbons from beneath the Earth's surface. These platforms can be fixed or floating and are designed to withstand harsh marine environments.
-
Mining Equipment
The development of mining equipment has been driven by the need to extract resources from increasingly difficult-to-reach locations and to process larger quantities of ore with greater efficiency.
-
Industrial Manufacturing
Today, the industry faces new challenges and opportunities, driven by technological advancements, globalization, and changing consumer demands.
-
Power Industry
With the growth of population and industrialization, the demand for electricity has been constantly increasing. This has led to the expansion and modernization of the power industry across the globe.
-
Building Automation
Building automation started with simple mechanical controls and has evolved into sophisticated digital systems that integrate various technologies to enhance building performance and occupant comfort.
Related Videos
-
DC solution
-
Motor protection solution
-
Electrical protection solution
-
Understand the importance of molded case circuit breakers: focus on DAM1 series
The importance of reliable, efficient molded case circuit breakers (MCCB) in electrical installations cannot be overstated. The DAM1 series circuit breakers stand out as the first choice for professio
-
Shanghai Dada Electrical's new product is now launched!
Welcome to the world of DC Circuit Breakers! These innovative devices are designed to protect distribution and group systems with various loads. From drives with moderate starting currents like compre
-
New motor protection circuit breaker by Shanghai Dada Electrical Co., Ltd.
Introducing the new motor protection circuit breaker by Shanghai Dada Electrical Co., Ltd. This essential device provides protection for motors against overloads and short circuits, ensuring the safet